30-3003 Explosion Proof Smoke Detector


30-3003
Explosion
Proof
Smoke Detector
Click
on the picture for a PDF Data Sheet for this device.
|
APPLICATION
The Protector Model
03 Explosion Proof Smoke Detector is a sensitive yet rugged,
state-of-the-art protection device that is designed for use
in hazardous industrial and commercial locations. The detector
is designed to operate effectively with both slow smoldering
and fast burning fires. Typical applications that use the
Model 03 include:
-
Combustible
storage facilities.
-
Munitions manufacturing.
-
Volatile chemical storage.
-
Chemical processing plants.
-
Petroleum refineries.
-
Turbine enclosures.
DESCRIPTION
The photoelectric smoke
detector uses a solid state infrared emitting diode (IRED)
and a light sensing photovoltaic cell arranged in a labyrinth
assembly. The labyrinth permits free access to smoke but restricts
external light. Because of its critical function to the operation
of the detector, each IRED is selected with extreme care and
is subjected to rigorous pre-production testing to ensure
long-term reliability and performance.
During normal operation
(no smoke), the detector samples the air approximately every
four seconds for a period of less than one millisecond. The
photovoltaic smoke cell, which is placed at an angle to the
pulsed invisible light source, is sensitive to the infrared
light in the specified frequency emitted by the IRED light
source and is designed to receive a signal only when the pulsed
IRED source is activated.
When smoke enters the
chamber, the light from the IRED reflects off the smoke particles
and reaches the photovoltaic smoke cell. When the amount of
light reflected by smoke reaches the factory set threshold
level, the smoke alarm circuit is actuated.
The detector will respond
to a slow smoldering fire when smoke in the chamber reaches
the preset sensitivity setting, typically 1.5%.
If a fast burning fire
should occur, including fires in flammable liquids and other
materials such as plastics that generate black smoke, the
abnormally rapid movement of smoke into the detection chamber
is sensed by a special rate compensating circuit. An increase
in smoke within the detection chamber that exceeds a preset
rate causes the rate compensation circuit to increase the
intensity of the light source, which increases detector sensitivity.
If the smoke continues to build at this rate, an amplifier
circuit is triggered and the unit generates an alarm. If not,
the detector reverts to normal sensitivity.
In normally smoky atmospheres
the detector will not go into alarm as long as the concentration
is less than the fixed sensitivity of the detector. This results
in a sensitive and positive response with the lowest potential
for unwanted alarms.
SPECIFICATIONS OPERATING
-
VOLTAGE
20 to 28 volts dc.
-
OPERATING
CURRENT
Standby:
10 milliamperes
Alarm: 35 milliamperes
-
MAXIMUM
AIR VELOCITY
feet
per minute.
-
RELAY
CONTACT RATING
2
amperes at 30 vdc. 0.5 ampere at 125 vac.
ENGINEERING SPECIFICATIONS
The detector shall
be a 1.5% fixed sensitivity photoelectric smoke detector,
providing minimum response time to all fire types.
The detection chamber
shall extend beyond the main housing into the area to be protected,
to provide maximum smoke entry capability into the chamber
from any direction.
The detector light
source shall be an IRED (Infrared Emitting Diode). Typical
detector current consumption in the standby condition shall
be 10 milliamperes.
The detector shall
lock in on alarm and have a visible alarm indicator LED.
The detector shall
have SPST alarm relay contacts for connection to the fire
alarm control panel and also power supervision contacts.
The detector enclosure
shall be an explosion-proof flanged housing designed to meet
NEC classifications of Class I, Groups C and D; Class II,
Groups E, F, and G; and Class III hazardous areas. The detector
shall be intended for surface mounting and connection to the
system wiring shall be by means of pigtails in a rated enclosure
(furnished).
EXPLOSION-PROOF
CERTIFICATION
The Model 03 is certified
by the German Electric Industry Association, VDE, to meet
Standards /"Special Protection" (Ex)sG5 (sand encapsulated),
for ignition groups EEx e II T5.
|
30-3003D Explosion Proof Smoke Detector


30-3003D
Explosion
Proof
Smoke Detector
Click
on the picture for a PDF Data Sheet for this device.
|
APPLICATION
The Pyrotector Model
03D Explosion-Proof Air Duct Smoke Detector is designed to
detect the presence of smoke for the primary purpose of controlling
blowers and dampers in air conditioning and ventilation systems
and is intended for use in hazardous industrial and commercial
locations. The unit mounts directly to heating, ventilating,
and air conditioning ducts and utilizes a cross sectional
sampling tube arrangement that allows large volume air sampling.
The Model 03D is intended to serve as a supplement rather
than a substitute for open area detection.
The
explosion-proof air duct smoke detector is intended to be
connected to a control unit and function as part of a fire
protection system. The 03D is designed for use with a 4-wire
system fire alarm control panel (2 wires for detector power
and 2 wires for detector output).
The
detector operates on the forward light scattering principle,
a technology that is based on more than 30 years of experience
in advanced photoelectric detection systems.
-
Explosion-proof
housing is designed for use in Division 1, Class I, Groups
C and D; Class II, Groups E, F, and G; Class III hazardous
locations.
-
Trouble-free
photoelectric operation. Standard 4-wire 24 vdc operation.
-
Designed
to meet ANSI/UL 268A smoke obscuration limits.
-
600
to ft/min airflow range.
-
Rugged
design for environmental extremes.
DESCRIPTION
The Model 03D uses
air sampling tubes to provide a cross sectional sampling of
air moving through the duct. Inlet sampling tubes are available
in four lengths: one foot, three feet, six feet, and ten feet.
The desired length must be specified when ordering.
The length of the inlet
sampling tube is determined by the width of the duct to be
monitored. The inlet duct should cover the entire width of
the duct, therefore, specify the shortest sampling tube that
is at least the width of the duct to be protected. It can
then be cut to the exact length at the job site.
Outlet tubes are one
common length. Both inlet and outlet tubes are furnished with
each detector.
EXPLOSION-PROOF
CERTIFICATION
The Model 03D is certified
by the German Electric Industry Association, VDE to meet standards
/"Special Protection" (EX)s G5 (sand encapsulated),
for ignition groups EExe11T5.
ENGINEERING SPECIFICATIONS
The explosion proof
air duct photoelectric smoke detector shall lock in on alarm
and have an alarm indicator LED visible through the air sampling
chamber cover. Detectors shall be mounted exterior to the
duct, with perforated sampling tubes. Activation of a detector
shall cause shutdown of associated equipment through the control
circuitry of the fire alarm panel. The detector shall be mounted
in a readily accessible location.
The detector shall
have SPST alarm contact for the fire alarm control panel and
power supervision. In addition, the detector shall be capable
of activating a remote indicating lamp on a remote annunciator.
The detector unit shall
be designed to meet NEC requirements for Class I, Groups C
and D; Class II, Groups E, F, and G; and Class III hazardous
locations. A rated junction box shall be furnished for connecting
the system wiring.
|
|